Features
- Single Channel, Single Cover
- Power devices mounted to body of raceway with mounting brackets or mounted to the raceway cover by two 6-32 screws
- Pre-cut, pre-wired, and pre-assembled to meet your specifications
- Extruded from #6063-T5 aluminum alloy
- 12", 18", 24" or custom cut snap-in covers
- Accommodate 15A and 20A square snap-in power devices
- Relief slots on either side for easier removal of covers and improved accessibility to all devices
- 12" receptacle pigtails provided for easy field connections
- Satin anodized finish or powder coated finish per your specifications at additional cost
- Fittings made from same durable and corrosion resistant anodized aluminum and miter cut to provide a uniform finish
Labeling
Front of Raceway
15A & 20A, 125V receptacles:
Label with panel and circuit identification
Back of Raceway
Label indicating raceway number, room/area, feed panel, raceway length and feed end.
Types of Labeling
- Standard
Silver self-adhesive ultraplate label
with black lettering.
- Engraving Directly on Raceway Cover
Black lettering engraved on aluminum
cover for an additional price.
- Engraved Phenolic Nameplates
Adhesive backed or screw mounted
black labels with white lettering for
an additional price.
Other colors are available for standard and phenolic nameplates.
Wiring Information
| Wire Type |
THNN Stranded |
|
| Wire Fill Chart |
| THNN Wire |
Capacity |
THHN Wire |
Capacity |
| 14 awg |
50 |
14 awg |
99 |
| 12 awg |
0 |
12 awg |
49 |
| 10 awg |
0 |
10 awg |
47 |
| 8 awg |
0 |
8 awg |
23 |
| 6 awg |
0 |
6 awg |
17 |
| With Receptacles |
Without Receptacles |
|
| Wire Gage |
15 amp #12 wire
20 amp #12 wire
30 amp #10 wire
50 amp #6 wire
60 amp #4 wire
|
Each ground wire entering the raceway will be connected to
the receptacle ground screw located within the raceway interior.
When isolated ground receptacles are required, a separate
green insulating grounding conductor connected only to
the receptacle terminal will be used.
Field grounding of the raceway is a requirement.
|
Color Coding
| Color Code for 125V, 2 Pole, 3 Wire, Grounding Receptacles |
| Ground Conductor: |
Green |
| Neutral Conductor: |
White |
| Hot Conductors: |
Black (A), Red (B), Blue (C) |
Each row of three circuits share a common neutral.
| Color Code for Other Receptacles |
| Ground Conductor: |
Green |
| Neutral Conductor: |
White |
| 1st Hot Conductor: |
X Black |
| 2nd Hot Conductor: |
Y Red |
| 3rd Hot Conductor: |
Z Blue |
|
| Odd Circuit Numbers |
| Phase A |
Phase B |
Phase C |
| 1 |
3 |
5 |
| 7 |
9 |
11 |
| 13 |
15 |
17 |
| 19 |
21 |
23 |
| 25 |
27 |
29 |
|
|
| Even Circuit Numbers |
| Phase A |
Phase B |
Phase C |
| 2 |
4 |
6 |
| 8 |
10 |
12 |
| 14 |
16 |
18 |
| 20 |
22 |
24 |
| 26 |
28 |
30 |
|
Device Compatibility
Snap in Single Square Receptacles