    Scope
    The contractor shall furnish and install a complete isolated power system as indicated on the plans and specified herein.

    Codes and Standards
    The isolated power system shall be designed and installed in accordance with the latest edition of the following codes and standards:

    • NFPA 99 "Health Care Facilities"
    • NFPA 70 "National Electrical Code"
    • UL Standard 1047 "Isolated Power System Distribution Equipment"
    • UL Standard 1022 "Line Isolation Monitors"
    Isolated Power Panel
    The isolated power panel shall be a PG LIFELINK Surgical Facility Panel. The panel shall be UL listed under Standard 1047 and shall incorporate the following features and components:
    1. Enclosure shall be a three-piece assembly consisting of back box, chassis and front trim. The back box shall be fabricated of galvanized steel in accordance with UL Standard 50, "Standard for Cabinets and Boxes" and shall be flush mounted, unless indicated otherwise, at the elevation shown on the plans. The back box for the Dual winding transformer will be no more than 10" deep. All internal electrical components shall be mounted on a galvanized steel chassis which bolts onto studs located in the back box. The front trim shall be made of 12 gauge stainless steel polished to a #4 satin finish and shall have a 1.5 inch return flange on all sides. It shall attach to the back box with a continuous piano hinge and be secured in the closed position with heavy-duty pawl fasteners.

    2. Dual Winding Isolation Transformer shall be single phase, 60 Hz, 15 KVA with ______ volt primary (specify 120, 208, 220, 240, 277, or 480). The transformer shall be of stacked core design with an electrostatic shield between the primary and secondary windings. The secondary side of the transformer will have two separate ungrounded windings independent of each other. Winding "A" will be ______ volt (specify 120, 208, 220, 240) and _______ KVA (specify 3, 5, or 7.5 ). Winding "B" will be ______ volt (specify 120, 208, 220, 240) and _______ KVA (specify 3, 5, or 7.5 ). The Dual secondary windings combined will equal no more than 15 KVA. Transformers 15 KVA shall not exceed 30 microamperes and 40 dB.

    3. Line Isolation Monitor (LIM) shall be the PG LIFELINK Mark IV self-testing and self-calibrating LIM. It shall continuously monitor the impedence from each secondary conductor to ground without the use of switching circuitry and shall display the total hazard current of the system on an ammeter. The LIM shall be capable of detecting all combinations of resistive and capacitive faults whether they are balanced, unbalanced or hybrid. The LIM shall contribute less than 15 microamperes to the total hazard current of the system. For Dual Winding panels two LIMs are required, one for each voltage required.

      The LIM shall alarm when the total hazard current (THC) reaches a value of 5 milliamperes (Ma). When the THC is less than 5Ma, a green light shall be illuminated indicating normal conditions. Should the THC reach 5Ma, a red light shall illuminate and an audible sound indicating an alarm. A silence switch shall be provided to quiet the buzzer while leaving the red light on. The yellow light will remain on while the LIM is in the silenced mode. The LIM shall automatically reset to normal status when the fault condition is corrected.

      The LIM shall also detect and signal an alarm if the ground connection to the LIM is broken. A momentary test switch shall be provided for periodic testing of the LIM circuitry.

      The LIM shall be flush mounted on the front of the panel so that the LIM signals are clearly visible at all times.

      The LIM shall be recognized under UL Standard 1022.

    4. Twin X-ray Illuminator shall be FLUSH mounted into panel front and shall have stainless steel trim. Each illuminator shall contain a 32 watt, circular lamp and low leakage ballast. Diffuser shall be white, translucent acrylic, 1/8 inch thick and shall slide up and out for easy access to the lamps. Illuminators shall be controlled by two-pole switch mounted on panel front.

    5. Elapsed time indicator shall be PG LIFELINK's DT and FLUSH mounted into panel front. The timer shall have a digital display, 2.5 inches high. The controls shall be mounted on the panel front. (OPTION—Dial elapsed timer can be furnished in lieu of digital timer. If desired, specify manufacturer and model number of dual elapsed timer.)

    6. Clock shall be PG LIFELINK's DC and FLUSH mounted into panel front. The clock shall have a digital display 2.5 inches high. (OPTION—Dial clock can be furnished in lieu of digital clock. If desired, specify manufacturer and model number of clock.)

    7. 120 volt Branch circuit breakers shall be 20 amp, two-pole, quantity _______ (15 max.). Only Bolt On Breakers will be considered with a secondary main breaker sized for 120 volt KVA selected.

    8. Primary main breaker will be 2 pole ______ amp

    9. Reference ground bus having 24 branch taps for #12 to #6 shall be provided.

    10. Power receptacles shall be provided on the front of the panel. Receptacles to be 20 amp, 120 volt, type __________ (specify), quantity __________ (8 max.).

    11. Ground jacks shall be provided on the front of the panel. Jacks to be Hampden SLR-3S, quantity _________ (8 max.).

    12. Provisions for connecting remote X-Ray / Laser receptacle to Dual Winding transformer. A 2 pole 240 volt, ______ amp, (Specify) branch breaker shall be provided for X-Ray /Laser receptacle.

    OPTIONS - Add the following if desired.

    1. An AM/FM CD player shall be incorporated into the panel. The system shall include an AM/FM stereo compact disc player, low voltage power supply and two 4-inch stereo speakers.


    2. OR stereo system shall include the following:
      • Support MP3 playback capability
      • Support Digital Satellite Radio capability
      • Have IR remote control

    Wiring
    All components within the isolation panel shall be prewired using low leakage type XHHW wire. A barriered compartment shall be provided for the incoming primary feeder and separation shall be maintained between grounded and ungrounded conductors. Terminal blocks shall be provided for connection of branch circuits and remote signal conductors.

    All branch circuit conductors of the isolated power system shall be stranded copper having a cross-linked polyethylene insulation, or equivalent with a dielectric constant of 3.5 or less. Type XHHW is suitable for this purpose. Each branch circuit conductor shall be color-coded in accordance with National Electrical code.

    Wire pulling compound produces an adverse effect upon the dielectric constant of conductor insulation and shall not be used when pulling the wire of the isolated power system.

    Accessories
    The following accessories are part of the isolated power system and are to be furnished where indicated on the plans.

    Remote X-Ray / Laser Receptacle, Model XO for X-Ray or LO for Laser _____(Specify) shall be furnished where indicated on plans. Module shall contain one receptacle _____ amp (Specify NEMA config.) mounted in an angular recessed compartment. A door over the recessed compartment shall conceal the receptacle when not in use. The front trim shall be made of stainless steel polished to a #4 satin finish and a galvanized steel back box.

    Power and Ground Module, Model RRP, shall be furnished where indicated on plans. Module shall contain _____ (specify quantity) Duplex power receptacles, and _____ (specify quantity) ground jacks. Devices shall be mounted on a stainless steel trim.

    Ground Module, Model RRP-04, shall be furnished where indicated on plans. Module shall contain four ground jacks mounted on a stainless steel front and shall include a galvanized steel back box. A copper ground bus with 16 terminals for wire sizes #14 to #6 and a #14 to #1/0 main lug shall be included.

    Master Ground Module, Model GJB 24, shall be furnished where indicated on the plans. Module shall consist of a galvanized steel back box, stainless steel front, and a copper ground bus with 24 terminals for wire sizes #14 to #6 and a #14 to #1/0 main lug.

    Furnish _____ (specify quantity) ground cord assemblies. Each cord shall be _____ feet long (specify 5, 8, 10, 12, 15, or 20 feet) and shall consist of an extra flexible copper grounding conductor insulated with green neoprene having a ground plug on one end and a ground lug on the other. Insulated Alligator Clips are available, specify if required.

    Test and Certification
    Upon completion of the installation, a qualified factory technician shall inspect and test the equipment to verify that it is properly installed and operating as specified. A field test report and written certification that the system was installed and operating properly shall be furnished. The factory technician shall also instruct the hospital personnel in the proper use and maintenance of the equipment.

    Approved Manufacturers
    This specification is based on equipment manufactured by PG LIFELINK. Products of other manufacturers will be considered provided they are equal in all respects and request for approval is submitted in writing to the engineer at least 10 days prior to the bid date.