Plus Series Laser Isolated Power Panel - Model IPL-P
The Plus Series Laser Isolated Power Panel (Model IPL-P) is a cost-effective way of providing high volt output (208V, 220V, or 240V) to power laser equipment in multiple operating rooms.
- One laser panel is centrally located near a group of operating rooms and can be connected to up to 12 laser outlets.
- A programmable logic controller (PLC) in the panel monitors load energized outlets and will not energize more than receptacles than transformer capacity.
Included with Laser Operating Room Isolated Power Supply Panel
- Up to 2 dedicated 208-240V isolated circuits for multiple ORs from a central panel
- Available in 10, 15 or 25 kVA capacity with up to 12 branch circuits (220V or 240V) with 30 or 50A circuits for portable laser devices.
- Laser Outlet Modules model DLO-R, including NEMA receptacle and LIM remote, are installed inside each OR
- PLC-based “Plug-Control” system automatically limits the number of energized circuits to minimize leakage current and avoid accidental shutdown

Panel Sizing
kVA Size Options | Back Box Size |
Max Weight |
10 | 565 | |
15 | 70"H x 36"W x 12"D | 685 |
25 |
Features
All Plus Series IPL-P Isolated Power Supply Systems include:
Hospital Grade Isolation Transformer:
- Supplies up to 12 each (208 or 240V, 30 or 50A) circuits for cord-connected, portable laser device loads
- Standard transformer sizes for each section range from 10, 15, or 25kVA for portable laser devices
- Primary input voltages available: 480, 277, 240, and 208V
- Secondary voltages available: 208,220, 240V
- Low leakage, electrostatically shielded primary and secondary windings
- 220°C Class R Insulation
- Top mounted, clamped and bolted design with anti-vibration mounting bushings for quiet operation
- Designed and built in accordance with UL and CSA Standards
- 50Hz available (optional)
Interior Chassis:
- Interior chassis built to order, fully assembled in the factory, and 100% tested
- Primary main circuit breaker
- Up to 12 factory installed 120V, two-pole, bolt-on branch circuit breakers*
- Copper ground bus
- Terminal strip for connecting Remote Annunciator(s)
- Customer may specify standard circuit breakers from Eaton, GE, Siemens, or Schneider Electric for consistent coordination or to maintain facility standard*
Enclosure and Trim:
- Heavy-duty galvanized steel back box designed for flush mounting; can be shipped ahead of interior during rough-in
- Stainless steel front trim panel with fully hidden hinged, door-in-door construction reduces damage and potential injuries during installation, testing, and maintenance
- Surface mounting options available
SafeDetec® Line Isolation Monitor (LIM):
- Industry's newest Line Isolation Monitor technology, providing advanced warning of faults to help reduce downtime and increase operational efficiencies
- Advanced filtering and noise suppression for improved accuracy and reliability
- High contrast 40-character LED display for better visibility and viewing angle
- Universal 120-240 VAC power input allows LIMs to be directly Interchanged from 120V to 208V/240V laser panels without changing the internal jumper or switch settings
- Additional parameters can be displayed on the user interface for more advanced troubleshooting, such as L1 and L2 line-to-ground voltages, insulation resistance, and insulation capacitance
- Increased memory allows more log entries and a longer history of LIM data
Available Accessory Outlet:
- At least one Laser Outlet Module is required for each branch circuit supplied by an XTL panel.
- Laser Outlet Modules include a user-specified NEMA receptacle, LIM Remote Annunciator, galvanized back box, and a stainless steel front trim with hinged door over the laser receptacle
- Standard configuration includes a Programmable Logic Controller (PLC) system.
- Optional non-controlled version available
- Optional “In-Use” light controls available
- Find more information on the Laser Outlet Module page
Installation
- Special low leakage wire should always be used for the powered conductors of branch circuit wiring. XPLE type insulation such as XHHW-2 wire is recommended with a dielectric constant of less than 3.5. Standard type insulation such as THHN is appropriate for the incoming primary and the ground wires only.
- The NEC (Article 517.160) requires secondary circuits to be colored brown and orange, with a distinctive stripe in a contrasting color. The brown wire is connected to the L2 bus and the hot side (brass screw) of a standard NEMA receptacle. The orange wire, L1 is connected to the silver screw where neutral would be connected. Polarity should be maintained throughout the installation.
- Conduit runs for branch circuits should be as short and direct as possible to minimize accumulated leakage current in the circuit conductors. Generally, 400‐450 feet is the maximum recommended cumulative length for all branch conductors from a single transformer. Avoid unnecessary bends and junctions.
- Do not use pulling compounds to lubricate inside of conduit. This will break down the insulation properties and raise leakage current. A dry talc powder may be used. It is typical to use conduit with a slightly larger diameter to ease pulling and avoid damage to wire insulation. An interior coating of PVC may also be used.
- Isolated power circuits must be kept separate from other circuits. Do not share conduit or raceway with non‐isolated circuits, or isolated circuits from another system.
- Each receptacle and equipment grounding connector must be connected back to Reference Ground Bus inside Isolation Panel to maintain Equipotential grounding system. If multiple panels serve the same space, they must be bonded together.
Technical Drawings
- Plus Series Model IPL-P Technical Drawing
- Plus Series Model IPL-P Technical Drawing with Additional Options
Product Downloads
- Plus Series Model Numbering Guide
- Plus Series Isolated Power Specifications
- Plus Series Isolated Power Systems Installation and Operation Manual
- Isolated Power Product Catalog
Certifications
PG LifeLink Laser Isolated IPL Power Panel is designed, built, and tested in accordance with the following:
CSA Certification
CSA C22.1 Part 1, and CSA C22.2 No. 204
HCAI (California Department of Health Care Access and Information)
OSP-0210-10
*Only PG LifeLink offers this as standard