Your browser is out of date.

You are currently using Internet Explorer 7/8/9, which is not supported by our site. For the best experience, please use one of the latest browsers.

Need a Schneider Panel Replacement Partner You Can Count On?

PG LifeLink delivers retrofits, LIM replacements, and service with unmatched speed and support.

Get a Replacement Quote

Line Isolation Monitors (LIM)

What is a Line Isolation Monitor (LIM)?

The Line Isolation Monitor (LIM) system is the central safety device of the Isolated Power Panel. The LIM is continuously monitoring the Total Hazard Current (THC) of all equipment powered by the panel. In the event of a line-to-ground fault an audible and visual signal will notify the medical staff of a potentially hazardous condition, but the patient is still protected. 

Isolated power systems maintain continuity of essential power to critical equipment in hospitals and surgery centers, and other “wet procedure locations” in the event of a line-to-ground fault.

In conjunction with the isolated power system, the LIM helps ensure uninterrupted power which is critical for equipment providing life support during surgery or intensive care. Additionally, the LIM is able to detect the first sign of electric fault and alert staff to help remove dangerously faulty equipment before it can create a safety risk.

Request a Quote

Why Isolated Power Is Used in Operating Rooms

Isolated Power is required in category 1 critical care  hospital operating rooms and other “wet procedure locations” because if a fault were to occur, the electric current will flow through the path of least resistance. In a “wet procedure location,” patients are vulnerable, critical electrical equipment is often used, and fluids are present. This combination creates a dangerous environment should an electrical fault occur.
 

No Intentional Bond to Ground

Isolated power systems are different from grounded systems because neither L1 nor L2 is tied to earth ground. This floating design creates high impedance, which allows the system to remain energized even when one fault condition exists.
 

Hazard Current

In a grounded system, leakage fault current flows directly to ground. In an isolated system, the LIM calculates predicted hazard current based on system impedance, it does not measure actual current flowing through the patient or equipment.

As more equipment and wiring are connected to the IPS, cumulative impedance decreases and calculated THC increases.

Continuous Impedance Monitoring

The LIM continuously measures line-to-ground impedance on L1 and L2 and displays THC in milliamps:
  • Higher impedance = Lower Hazard Current
  • Lower impedance = Higher Hazard Current
This real-time calculation enables early warning of insulation degradation before a dangerous condition could occur.
 

First Fault Alarm at 5mA 

When the Total Hazard Current exceeds 5 mA, the LIM activates an audible and visual alarm. This indicates a first fault condition. Importantly:
  • The alarm does not mean a dangerous current is flowing.
  • It does not mean equipment should be immediately shut down.
  • It does not interrupt power to the room.
An alarm indicated that one layer of isolation had been compromised and that a second fault could now allow hazardous current to flow. This is the key advantage of isolation power systems: The first fault does not trip a breaker or shut down critical equipment.
 

Why the System Stays Energized

Unlike Ground-Fault Circuit Interrupters (GFICs) that trips on imbalance, isolated power systems limit potential fault current by maintaining high impedance, allowing essential systems to remain energized during a first fault.

Need Help? Explore Our Resources

Line Isolation Monitor FAQs

An alarm indicates that a ground fault has occurred somewhere in the isolated power system. This could be due to faulty equipment, wiring issues, or excessive leakage currents caused by too many devices connected to the system. If your LIM enters an alarm, follow the troubleshooting steps below or call PG LifeLink Field Service at 877-445-4123 for assistance.      

  • An alarm does not mean there is imminent danger. Do not endanger patient by discontinuing procedure prematurely.
  • If possible, immediately notify personnel responsible for maintaining equipment.
  • If it is clear that the alarm is directly related to a particular device, disconnect that device from the system. Depending on the nature of the device, this may not be possible. For example, life-support equipment.
  • Once the procedure is completed and the patient has been safely removed from the area, authorized personnel should attempt to identify the root cause of the fault. Likely causes may include damaged wire or power cord insulation, liquid intrusion into energized equipment or wiring, or faulty equipment.
  • If the cause is not readily identifiable, turn off all circuit breakers on the isolation power panel. Then turn on individual circuit breakers one at a time and observe the circuit’s relative hazard current contribution as displayed on the LIM. Identify which circuits contribute the largest amount of hazard current. This will narrow down the number of devices that may be associated with the alarm.
  • Contact PG LifeLink Field Service for further troubleshooting at 877-445-4123 or click here to email a customer service rep.
Yes. A first fault condition does not interrupt power and does not mean hazardous current is actively flowing. The purpose of the isolated power system is to allow procedures to continue while the issue is identified and corrected.

Questions? Contact Us

Please give us a call at 800-287-4123 or fill out the form below and our team will be in touch as soon as possible. * marks required fields.